GeneratorsChecklists & Templates

Generator Compliance Checklist for Facility Managers

Printable generator compliance checklist covering NFPA 110 and EPA requirements with inspection prep guidance for facility managers.

By FCH Editorial Team·March 15, 2026·15 min read

How to Use This Checklist

This compliance checklist is designed to serve as a working document for facility managers responsible for emergency generator systems. It covers the inspection, testing, maintenance, and documentation requirements established by NFPA 110 (Standard for Emergency and Standby Power Systems), the EPA RICE NESHAP (40 CFR Part 63, Subpart ZZZZ), and common AHJ expectations.

Each item includes a reference to the applicable code section so you can verify requirements against the current edition of the standard. Use this checklist in three ways:

  1. As a routine audit tool to verify your ongoing maintenance program covers all required items
  2. As an inspection preparation guide when you know an AHJ visit is scheduled
  3. As a gap analysis to identify areas where your current program may be deficient

Items are organized by inspection frequency. The status column uses the following indicators:

  • Pass = Item meets requirements
  • Fail = Item does not meet requirements and needs corrective action
  • N/A = Item does not apply to this installation

Weekly Visual Inspection Checklist

These items should be verified at intervals not exceeding seven days per NFPA 110 Section 8.3.4.

#Inspection ItemCode ReferenceStatus
W-1Generator room or enclosure is clean and free of stored materialsNFPA 110, 8.3.4______
W-2No visible fuel, oil, or coolant leaks presentNFPA 110, 8.3.4______
W-3Engine block heater is energized and maintaining temperature above 100degFNFPA 110, 8.3.4______
W-4Battery charger is operating and indicating float chargeNFPA 110, 8.3.7______
W-5Generator control panel shows no active alarms or fault codesNFPA 110, 8.3.4______
W-6Ventilation louvers and air intake are unobstructedNFPA 110, 7.9______
W-7Exhaust discharge point is clear and unobstructedNFPA 110, 7.9______
W-8Emergency shutdown controls are accessible and properly labeledNFPA 110, 7.5______
W-9Fire extinguisher is present, accessible, and current on inspectionNFPA 10______
W-10Hour meter reading recorded in operations logNFPA 110, 8.3.4______
W-11Fuel level in day tank and main storage tank is adequateNFPA 110, 7.9______
W-12Generator room door(s) secure with proper signageLocal codes______

Efficiency Tip

Create a laminated copy of the weekly checklist and mount it on a clipboard near the generator. Technicians can mark items with a dry-erase marker during rounds, then transfer results to the permanent log. This takes less than 20 minutes per week and is the single most effective compliance habit you can establish.

Monthly Exercise and Testing Checklist

Monthly testing under load is required by NFPA 110 Section 8.4.2. This checklist covers both the exercise test and associated monthly inspections.

#Inspection/Test ItemCode ReferenceStatus
M-1Generator exercised under load for minimum 30 minutesNFPA 110, 8.4.2______
M-2Load during exercise was at least 30% of nameplate kW ratingNFPA 110, 8.4.2.1______
M-3ATS initiated automatic transfer on simulated power lossNFPA 110, 8.4.2______
M-4ATS completed retransfer after power restorationNFPA 110, 8.4.2______
M-5Generator started within 10 seconds (Level 1 systems)NFPA 110, 4.1.1______
M-6Output voltage within plus or minus 2% of rated voltage (all phases)NFPA 110, 4.3______
M-7Output frequency stable at 60 Hz plus or minus 0.5 HzNFPA 110, 4.3______
M-8Engine oil pressure within manufacturer specificationManufacturer______
M-9Coolant temperature stabilized within normal operating rangeManufacturer______
M-10Engine oil level is at or near full markNFPA 110, 8.3.4______
M-11Coolant level is adequate in expansion tank or radiatorNFPA 110, 8.3.4______
M-12Drive belts in serviceable condition (no cracks, glazing, or fraying)NFPA 110, 8.3.4______
M-13Coolant and fuel hoses in serviceable conditionNFPA 110, 8.3.4______
M-14Air filter restriction within acceptable limitsManufacturer______
M-15All exercise test parameters recorded in operations logNFPA 110, 8.4.2______
M-16Reason for operation and hours logged for EPA tracking40 CFR 63, Subpart ZZZZ______

Important

If your building loads do not consistently reach 30% of the generator's nameplate rating during monthly tests, you must either add supplemental loads via a load bank or document why the actual building load is representative. AHJ inspectors will verify that your monthly test records show adequate loading. Consistent no-load or light-load testing is a common citation.

Quarterly Inspection Checklist

Quarterly items address slower-degrading components and systems that require periodic verification beyond the monthly cycle.

#Inspection/Test ItemCode ReferenceStatus
Q-1Starting battery load test or impedance test performedNFPA 110, 8.3.7______
Q-2Battery terminals cleaned, tight, and treated for corrosionNFPA 110, 8.3.7______
Q-3Battery electrolyte levels checked (flooded cells) or case integrity verified (VRLA)NFPA 110, 8.3.7______
Q-4Coolant freeze point and pH tested; SCA concentration verifiedManufacturer______
Q-5Exhaust system inspected for leaks, corrosion, and loose connectionsNFPA 110, 8.3.4______
Q-6All emergency stop buttons tested and verified functionalNFPA 110, 7.5______
Q-7Engine and alternator vibration isolators inspectedNFPA 110, 8.3.4______
Q-8Fuel system inspected for leaks, including day tank and transfer pipingNFPA 110, 8.3.4______
Q-9ATS exercised in manual mode to verify manual transfer capabilityNFPA 110, 8.4.3______

Annual Comprehensive Inspection Checklist

Annual tasks include the most thorough inspections and the critical full-load bank test. These items are typically performed by qualified service technicians.

#Inspection/Test ItemCode ReferenceStatus
A-1Full load bank test at 100% of nameplate kW for minimum 2 hoursNFPA 110, 8.4.2.3______
A-2All load bank test parameters recorded at 15-minute intervalsNFPA 110, 8.4.2.3______
A-3Engine oil and filters changedManufacturer______
A-4Fuel filters replaced (primary and secondary)Manufacturer______
A-5Air filter element replacedManufacturer______
A-6Cooling system flushed and refilled with fresh coolantManufacturer______
A-7Thermostat tested or replacedManufacturer______
A-8Comprehensive ATS inspection: contacts, sensing, timing, bypassNFPA 110, 8.4.3______
A-9Fuel quality tested per ASTM D975 standardsNFPA 110, 8.3.4______
A-10Fuel tank cleaned or polished to remove water and contaminantsNFPA 110, 8.3.4______
A-11Alternator insulation resistance tested (megohmmeter, minimum 2 megohms)IEEE 43 / Manufacturer______
A-12All power electrical connections torqued to specificationNFPA 70, 110.14______
A-13All engine protection sensors verified for calibration and functionManufacturer______
A-14Starting batteries replaced if beyond service life (3 years VRLA, 5 years flooded)NFPA 110, 8.3.7______
A-15Generator enclosure or room weatherproofing and seals inspectedNFPA 110, 7.2______
A-16All signage verified current and legibleLocal codes______

Documentation Readiness Checklist

AHJ inspectors will review your documentation as thoroughly as they inspect the physical equipment. Ensure the following records are complete and accessible before any inspection.

#Documentation ItemCode ReferenceStatus
D-1Operations log with all start/stop events, hours, and reasons for operationNFPA 110, 8.3.4______
D-2Maintenance log with all PM activities, parts, and technician informationNFPA 110, 8.3.4______
D-3Monthly exercise test records showing date, duration, load, and operating parametersNFPA 110, 8.4.2______
D-4Annual load bank test reportNFPA 110, 8.4.2.3______
D-5EPA operating hour log with emergency/non-emergency classification for each event40 CFR 63, Subpart ZZZZ______
D-6Total non-emergency operating hours year-to-date (must not exceed 100 hours)40 CFR 63, Subpart ZZZZ______
D-7Fuel purchase records confirming ULSD (15 ppm sulfur maximum)40 CFR 63, Subpart ZZZZ______
D-8Current fuel quality test reportASTM D975______
D-9Oil analysis reports (if enrolled in oil analysis program)Best practice______
D-10ATS inspection and test recordsNFPA 110, 8.4.3______
D-11Battery test records (quarterly load tests or impedance tests)NFPA 110, 8.3.7______
D-12Generator nameplate data sheet (kW rating, voltage, engine serial number, EPA Tier)NFPA 110, 7.1______
D-13Copy of operating permit or registration (if required by state/local authority)State/local______
D-14Manufacturer's operation and maintenance manual on-siteNFPA 110, 8.3.4______
D-15Previous AHJ inspection reports with corrective action documentationBest practice______

EPA Compliance Verification Items

These items specifically address EPA RICE NESHAP requirements for emergency stationary compression-ignition engines.

#EPA Compliance ItemRegulatory ReferenceStatus
E-1Engine classified as emergency per 40 CFR 63.6675 definition40 CFR 63, Subpart ZZZZ______
E-2Non-resettable hour meter installed and operational40 CFR 63, Subpart ZZZZ______
E-3Total non-emergency hours tracked and under 100-hour annual limit40 CFR 63.6640______
E-4Only ULSD fuel used (15 ppm sulfur maximum)40 CFR 63.6604______
E-5Maintenance performed per manufacturer recommendations40 CFR 63.6603______
E-6Operating records maintained for minimum 5 years40 CFR 63.6660______
E-7Initial notification submitted to delegated authority (if required)40 CFR 63.6645______
E-8Engine EPA Tier certification documented40 CFR Part 1039______
E-9State/local air quality permit obtained (if required for engine size)State SIP______
E-10DEF system functional and fluid level adequate (Tier 4 Final engines)Manufacturer______
E-11DPF regeneration system functional (Tier 4 Final engines)Manufacturer______

Red Flag Items: Common Causes of Failed Inspections

AHJ inspectors see the same deficiencies repeatedly. The following items represent the most common reasons generators fail compliance inspections. Address these proactively to avoid citations.

Critical Red Flags

Red FlagWhy It FailsHow to Fix It
No monthly test recordsNFPA 110 Section 8.4.2 is explicit about monthly testing. Missing records are treated as missing testsImplement monthly testing immediately; backfilling records is not acceptable
Light-load or no-load testing onlyRunning the generator without at least 30% load does not satisfy NFPA 110 Section 8.4.2.1Arrange for a portable load bank if building loads are insufficient
Dead or weak starting batteriesBatteries are the most common single point of failure. AHJ inspectors may witness a start attemptTest batteries quarterly; replace proactively based on age and test results
No annual load bank test reportThe annual full-load test per NFPA 110 Section 8.4.2.3 is a specific, documented requirementSchedule and perform the test; retain the detailed report with 15-minute interval data
Missing operations logInspectors expect to see a chronological record of every operating eventStart a log immediately; maintain it consistently going forward
Block heater not functioningA cold engine may fail to start within the required 10-second window for Level 1 systemsCheck block heater operation weekly; replace immediately if failed
Fuel quality not testedDegraded diesel fuel causes injector failure, filter clogging, and starting problemsTest fuel annually per ASTM D975; implement fuel polishing if quality is marginal
ATS not tested independentlyThe transfer switch must be tested as part of the monthly exercise; many facilities skip the retransfer verificationInclude full ATS cycle (transfer and retransfer) in every monthly test
EPA hour tracking absentInability to demonstrate compliance with the 100-hour non-emergency limit is a regulatory violationRecord hours and classify each operating event as emergency or non-emergency
Stored materials in generator roomCombustible storage near a diesel engine and fuel system is a fire code violationRemove all non-essential items; post signage prohibiting storage

Immediate Action Required

If any of the critical red flag items above apply to your facility, address them before your next AHJ inspection. Multiple red flag findings in a single inspection can trigger more frequent follow-up inspections, increased scrutiny, and in some jurisdictions, fines or requirements for third-party commissioning.

How to Prepare for an AHJ Inspection

When you know an AHJ inspection is approaching, or as part of your routine annual preparation, follow this structured approach to maximize your chances of a clean inspection.

30 Days Before the Inspection

  1. Complete your annual maintenance. Perform the full annual service, including the load bank test, before the inspection date. Having fresh service records demonstrates active compliance.

  2. Audit your documentation. Walk through the Documentation Readiness Checklist above. Identify and fill any gaps. Organize records chronologically and make them easy to navigate.

  3. Conduct a self-inspection. Use the weekly, monthly, quarterly, and annual checklists in this guide to perform a thorough self-assessment. Document any deficiencies found and the corrective actions taken.

  4. Verify all signage. Confirm that generator room signage, emergency shutdown labels, and hazard warnings are in place, legible, and compliant with local requirements.

  5. Clean the generator area. Remove any stored items, sweep the floor, clean up oil drips, and ensure the space looks well-maintained. First impressions set the tone for the entire inspection.

The Day of the Inspection

  1. Have documentation ready. Print or prepare digital access to your operations log, maintenance log, test records, fuel receipts, and permits. Do not make the inspector wait while you search for records.

  2. Assign an escort. Designate a knowledgeable staff member to accompany the inspector. This person should be able to explain your maintenance program, answer questions about operating history, and demonstrate generator operation if requested.

  3. Be prepared for a witnessed start. Many AHJ inspectors will want to see the generator start and the ATS transfer. Verify that the system is in automatic mode and ready for a live demonstration.

  4. Know your system. Be prepared to state the generator's kW rating, voltage configuration, fuel type, EPA Tier, and installation date. Know the nameplate details of your ATS. Inspectors respect facility managers who understand their systems.

  5. Do not argue findings. If the inspector identifies a deficiency, acknowledge it professionally and ask for clarification on the required corrective action. Request the finding in writing with the specific code reference. Disputes are resolved through the appeals process, not during the inspection.

After the Inspection

  1. Review the inspection report carefully for accuracy and completeness.
  2. Develop a corrective action plan for any cited deficiencies, with specific timelines and responsible parties.
  3. Complete corrective actions before the deadline specified by the AHJ.
  4. Document the corrective actions taken, including photographs where applicable.
  5. Submit documentation of corrective actions to the AHJ if required.
  6. Update your maintenance program to prevent recurrence of any cited deficiencies.

Maintaining Ongoing Compliance

Compliance is not a once-a-year event that coincides with your AHJ inspection. It is the result of a disciplined, year-round program that integrates inspection, testing, maintenance, and documentation into your regular facility management operations.

The checklists in this guide provide the framework. Your job as a facility manager is to assign responsibility, establish accountability, and verify execution. When your program runs consistently throughout the year, AHJ inspections become confirmations of what you already know: your emergency power system is compliant, well-maintained, and ready to protect your facility and its occupants.

Important Disclaimer

The information provided in this article is intended for general educational purposes only and should not be considered legal, regulatory, or professional compliance advice. Content is based primarily on national standards including NFPA (National Fire Protection Association), EPA (Environmental Protection Agency), ASHRAE, and ICC (International Code Council) publications current as of the date of publication.

Compliance requirements vary significantly by state, county, and municipality. Local Authorities Having Jurisdiction (AHJs) may adopt, amend, or supplement national codes with additional requirements. Always verify applicable requirements with your local AHJ, a licensed professional engineer, or a qualified compliance consultant before making compliance decisions for your facility.

FacilityComplianceHub.org and its sponsors assume no liability for actions taken based on the information presented on this site.

Buffalo Power Solutions

This guide is brought to you by our Platinum Sponsor

Buffalo Power Solutions

Schedule a Free Compliance Assessment

Related Articles