GeneratorsChecklists & Templates

Generator Compliance Checklist for Facility Managers

Printable generator compliance checklist covering NFPA 110 and EPA requirements with inspection prep guidance for facility managers.

By FCH Editorial Team·Updated September 24, 2026·18 min read

How to Use This Checklist

This compliance checklist is designed to serve as a working document for facility managers responsible for emergency generator systems. It covers the inspection, testing, maintenance, and documentation requirements established by NFPA 110 (Standard for Emergency and Standby Power Systems), the EPA RICE NESHAP (40 CFR Part 63, Subpart ZZZZ), the stationary diesel engine NSPS (40 CFR Part 60, Subpart IIII), and common AHJ expectations.

Where an item comes directly from a code or regulation, the reference column cites it. NFPA 110 section numbers are from the 2010 edition, which CMS enforces for healthcare facilities through NFPA 99-2012; numbering can differ in the edition your AHJ has adopted (the current edition is 2025). Items marked "Manufacturer" or "Best practice" are not specific code requirements but are part of a sound maintenance program. For the full testing requirements, see our NFPA 110 compliance guide. Use this checklist in three ways:

  1. As a routine audit tool to verify your ongoing maintenance program covers all required items
  2. As an inspection preparation guide when you know an AHJ visit is scheduled
  3. As a gap analysis to identify areas where your current program may be deficient

Items are organized by inspection frequency. The status column uses the following indicators:

  • Pass = Item meets requirements
  • Fail = Item does not meet requirements and needs corrective action
  • N/A = Item does not apply to this installation

Weekly Visual Inspection Checklist

NFPA 110 requires the emergency power supply system (EPSS), including transfer switches, to be inspected weekly (Section 8.4.1). A weekly walk-around typically covers the items below.

#Inspection ItemCode ReferenceStatus
W-1Generator room or enclosure is clean and free of stored materialsNFPA 110 (EPS room not used for unrelated purposes)______
W-2No visible fuel, oil, or coolant leaks presentNFPA 110, 8.4.1______
W-3Engine block heater is energized and maintaining the temperature the manufacturer specifiesNFPA 110 (engine heating); Manufacturer______
W-4Battery charger is operating and indicating normal chargeNFPA 110, 8.4.1______
W-5Generator control panel shows no active alarms or fault codesNFPA 110, 8.4.1______
W-6Ventilation louvers and air intake are unobstructedNFPA 110, 8.4.1______
W-7Exhaust discharge point is clear and unobstructedNFPA 110, 8.4.1______
W-8Emergency shutdown controls are accessible and properly labeledManufacturer; local codes______
W-9Fire extinguisher is present, accessible, and current on inspectionNFPA 10; local fire code______
W-10Hour meter reading recorded in operations logBest practice; supports EPA hour records______
W-11Fuel level in day tank and main storage tank meets the quantity required for your EPSS ClassNFPA 110, 8.4.1______
W-12Transfer switch inspected (position, indicators, no alarms)NFPA 110, 8.4.1______
W-13Generator room door(s) secure with proper signageLocal codes______

Efficiency Tip

Create a laminated copy of the weekly checklist and mount it on a clipboard near the generator. Technicians can mark items with a dry-erase marker during rounds, then transfer results to the permanent log. A consistent weekly routine is one of the simplest compliance habits you can establish.

Monthly Exercise and Testing Checklist

NFPA 110 requires diesel generator sets to be exercised under load at least monthly for at least 30 minutes (Section 8.4.2). Healthcare facilities must run the monthly test 12 times a year at intervals of not less than 20 days and not more than 40 days. This checklist covers the exercise test and associated monthly inspections.

#Inspection/Test ItemCode ReferenceStatus
M-1Generator exercised under load for minimum 30 minutes (cool-down not counted)NFPA 110, 8.4.2______
M-2Load was at least 30% of nameplate kW, or maintained the manufacturer's minimum exhaust gas temperatureNFPA 110, 8.4.2______
M-3Transfer switch operated from normal to emergencyNFPA 110, 8.4.6______
M-4Transfer switch completed retransfer to normalNFPA 110, 8.4.6______
M-5Power restored to load terminals within 10 seconds (Type 10 systems)NFPA 110 (Type 10); NEC 700______
M-6Output voltage within the manufacturer's specified range (all phases)Manufacturer______
M-7Output frequency within the manufacturer's specified rangeManufacturer______
M-8Engine oil pressure within manufacturer specificationManufacturer______
M-9Coolant temperature stabilized within normal operating rangeManufacturer______
M-10Engine oil level is at or near full markManufacturer______
M-11Coolant level is adequate in expansion tank or radiatorManufacturer______
M-12Drive belts in serviceable condition (no cracks, glazing, or fraying)Manufacturer______
M-13Coolant and fuel hoses in serviceable conditionManufacturer______
M-14Air filter restriction within acceptable limitsManufacturer______
M-15Starting batteries inspected and testedNFPA 110, 8.3.7.1______
M-16All exercise test parameters (date, duration, kW load, readings) recorded in the logNFPA 110 records requirements______
M-17Hours of operation logged and classified as emergency or non-emergency for EPA tracking40 CFR 63.6655(f); 40 CFR 60.4214(b)______

Important

If your diesel generator's monthly tests do not reach 30% of nameplate kW or the manufacturer's minimum exhaust gas temperature, NFPA 110 still requires monthly exercise with the available load, plus an annual supplemental load test: at least 30 minutes at 50% of nameplate followed by at least 60 minutes at 75% (Section 8.4.2.3). Consistent light-load testing without the supplemental test is a common finding.

Quarterly Inspection Checklist

NFPA 110 does not set a separate quarterly inspection list, but quarterly checks are a practical way to cover slower-degrading components between monthly tests and annual service.

#Inspection/Test ItemCode ReferenceStatus
Q-1Battery terminals cleaned, tight, and treated for corrosionManufacturer______
Q-2Battery electrolyte levels checked (flooded cells) or case integrity verified (sealed batteries)Manufacturer______
Q-3Coolant freeze point and condition tested; additive concentration verifiedManufacturer______
Q-4Exhaust system inspected for leaks, corrosion, and loose connectionsManufacturer______
Q-5Emergency stop buttons tested and verified functionalManufacturer______
Q-6Engine and alternator vibration isolators inspectedManufacturer______
Q-7Fuel system inspected for leaks, including day tank and transfer pipingManufacturer______
Q-8Transfer switch manual operation capability verifiedManufacturer______

Annual Comprehensive Inspection Checklist

Annual tasks include the most thorough inspections and, where required, supplemental load testing. These items are typically performed by qualified service technicians.

#Inspection/Test ItemCode ReferenceStatus
A-1Supplemental load test (30 min at 50%, then 60 min at 75% of nameplate) if monthly tests did not meet the loading criterionNFPA 110, 8.4.2.3______
A-2Load test readings recorded throughout the testNFPA 110 records requirements______
A-3Engine oil and filter changed (existing emergency engines at area sources: every 500 hours or annually)Manufacturer; 40 CFR 63 Subpart ZZZZ, Table 2d______
A-4Fuel filters replaced (primary and secondary)Manufacturer______
A-5Air cleaner inspected and replaced as necessary (every 1,000 hours or annually for existing emergency engines at area sources)Manufacturer; 40 CFR 63 Subpart ZZZZ, Table 2d______
A-6All hoses and belts inspected and replaced as necessary (every 500 hours or annually for existing emergency engines at area sources)40 CFR 63 Subpart ZZZZ, Table 2d______
A-7Cooling system serviced per manufacturer scheduleManufacturer______
A-8Comprehensive transfer switch maintenance: contacts, sensing, timing, bypassManufacturer______
A-9Fuel quality tested using ASTM standards or manufacturer's recommendationsNFPA 110, 8.3.8______
A-10Fuel tank cleaned or fuel polished if testing shows water or contaminationBest practice______
A-11Alternator insulation resistance tested and compared with manufacturer criteria and prior readingsManufacturer______
A-12Power electrical connections inspected and torqued to specificationManufacturer______
A-13Engine protection sensors verified for calibration and functionManufacturer______
A-14Starting batteries replaced if test results or age warrant, per manufacturer recommendationsNFPA 110, 8.3.7.1; Manufacturer______
A-15Generator enclosure or room weatherproofing and seals inspectedBest practice______
A-16All signage verified current and legibleLocal codes______
A-17Level 1 systems: 4-hour load test completed within the last 36 monthsNFPA 110, 8.4.9______

Documentation Readiness Checklist

AHJ inspectors will review your documentation as thoroughly as they inspect the physical equipment. Ensure the following records are complete and accessible before any inspection.

#Documentation ItemCode ReferenceStatus
D-1Operations log with all start/stop events, hours, and reasons for operationNFPA 110 records requirements______
D-2Maintenance log with all PM activities, parts, and technician informationNFPA 110 records requirements______
D-3Monthly exercise test records showing date, duration, load, and operating parametersNFPA 110, 8.4.2______
D-4Annual supplemental load test report (if required) and most recent 36-month test report (Level 1)NFPA 110, 8.4.2.3 and 8.4.9______
D-5EPA operating hour log from the non-resettable hour meter, with emergency/non-emergency classification and the reason for each emergency run40 CFR 63.6655(f)______
D-6Year-to-date maintenance/testing plus non-emergency hours (100-hour limit), with non-emergency situations separately (50-hour limit)40 CFR 63.6640(f); 40 CFR 60.4211(f)______
D-7Fuel records showing fuel meets applicable specifications, including 15 ppm nonroad diesel where required40 CFR 60.4207(b); 40 CFR 63.6604______
D-8Current fuel quality test reportNFPA 110, 8.3.8______
D-9Oil analysis reports (if used to extend Table 2d oil change intervals)40 CFR 63.6625(i)______
D-10Transfer switch inspection and test recordsNFPA 110, 8.4.1 and 8.4.6______
D-11Battery inspection and test recordsNFPA 110, 8.3.7.1______
D-12Generator nameplate data (kW rating, voltage, engine serial number, model year, EPA certification)Best practice______
D-13Copy of operating permit or registration (if required by state/local authority)State/local______
D-14Manufacturer's operation and maintenance manual on-siteBest practice______
D-15Previous AHJ inspection reports with corrective action documentationBest practice______

EPA Compliance Verification Items

These items address federal requirements for emergency stationary compression-ignition (diesel) engines. Existing engines at area sources (most commercial sites) follow Subpart ZZZZ directly; new or reconstructed engines at area sources comply with Subpart ZZZZ by meeting NSPS Subpart IIII (40 CFR 63.6590(c)). See our guide to EPA emissions standards for backup generators for details.

#EPA Compliance ItemRegulatory ReferenceStatus
E-1Engine meets the definition of an emergency engine and is operated within the emergency limits40 CFR 63.6675; 40 CFR 63.6640(f)______
E-2Non-resettable hour meter installed and operational40 CFR 63.6625(f); 40 CFR 60.4209(a)______
E-3Maintenance/testing plus non-emergency hours at or under 100 per calendar year, with non-emergency situations at or under 5040 CFR 63.6640(f); 40 CFR 60.4211(f)______
E-4Diesel fuel meets 40 CFR 1090.305 nonroad specification where required (new NSPS engines; existing engines over 100 hp used under the financial-arrangement provision)40 CFR 60.4207(b); 40 CFR 63.6604(b)______
E-5Engine operated and maintained per manufacturer's emission-related instructions or your own maintenance plan40 CFR 63.6625(e); 40 CFR 60.4211(a)______
E-6Table 2d management practices completed (existing engines at area sources)40 CFR 63.6603(a); Table 2d______
E-7Records kept for at least 5 years40 CFR 63.6660______
E-8Notification status confirmed (initial notification not required for existing emergency engines at area sources or for emergency engines under NSPS Subpart IIII)40 CFR 63.6645(a)(5); 40 CFR 60.4214(b)______
E-9Engine EPA certification documented (2007 and later emergency engines certified to Tier 2 or Tier 3 standards for their model year and power)40 CFR 60.4202; 40 CFR 60.4205(b)______
E-10State/local air quality permit or registration obtained (if required)State/local______
E-11DPF backpressure monitor functional and corrective actions recorded (engines with a DPF)40 CFR 60.4209(b); 40 CFR 60.4214(c)______
E-12DEF system functional and fluid level adequate (engines with SCR)Manufacturer______

Red Flag Items: Common Causes of Failed Inspections

The following items are common reasons generators draw findings during inspections. Address these proactively to avoid citations.

Critical Red Flags

Red FlagWhy It FailsHow to Fix It
No monthly test recordsNFPA 110 Section 8.4.2 requires monthly exercise, and missing records are usually treated as missing testsImplement monthly testing immediately; never backfill records
Light-load testing without a supplemental testMonthly tests below 30% of nameplate (or the manufacturer's minimum exhaust temperature) require an annual supplemental load test under Section 8.4.2.3Arrange for a portable load bank for the annual test, or add load to monthly tests
Dead or weak starting batteriesBatteries are a frequent cause of failure to start, and inspectors may witness a start attemptInspect and test batteries on the NFPA 110 schedule; replace based on test results and age
No supplemental or 36-month test reportWhere required, the annual supplemental test (8.4.2.3) and the Level 1 36-month, 4-hour test (8.4.9) must be documentedSchedule and perform the test; retain the detailed report
Missing operations logInspectors expect a chronological record of every operating eventStart a log immediately; maintain it consistently going forward
Block heater not functioningA cold engine may not start and accept load within 10 seconds on a Type 10 systemCheck block heater operation weekly; repair immediately if failed
Fuel quality not testedNFPA 110 requires an annual fuel quality test, and degraded fuel causes filter clogging and starting problemsTest fuel annually using ASTM standards or the manufacturer's recommendations; remediate if quality is marginal
Transfer switch not fully testedTransfer switches must be operated monthly; many facilities skip retransfer verificationInclude the full transfer and retransfer cycle in every monthly test
EPA hour tracking absentHour records separating emergency and non-emergency operation are required, and without them you cannot show the engine qualifies as emergencyRecord hours from the hour meter and classify each operating event
Stored materials in generator roomNFPA 110 does not permit the EPS room to be used for unrelated purposes, and combustible storage is a fire hazardRemove all non-essential items; post signage prohibiting storage

Immediate Action Required

If any of the critical red flag items above apply to your facility, address them before your next AHJ inspection. Multiple findings in a single inspection can lead to follow-up inspections, increased scrutiny, and in some jurisdictions, fines.

How to Prepare for an AHJ Inspection

When you know an AHJ inspection is approaching, or as part of your routine annual preparation, follow this structured approach to maximize your chances of a clean inspection.

30 Days Before the Inspection

  1. Complete your annual maintenance. Perform the annual service, including any required supplemental load test, before the inspection date. Having fresh service records demonstrates active compliance.

  2. Audit your documentation. Walk through the Documentation Readiness Checklist above. Identify and fill any gaps. Organize records chronologically and make them easy to navigate.

  3. Conduct a self-inspection. Use the weekly, monthly, quarterly, and annual checklists in this guide to perform a thorough self-assessment. Document any deficiencies found and the corrective actions taken.

  4. Verify all signage. Confirm that generator room signage, emergency shutdown labels, and hazard warnings are in place, legible, and compliant with local requirements.

  5. Clean the generator area. Remove any stored items, sweep the floor, clean up oil drips, and ensure the space looks well-maintained. First impressions set the tone for the entire inspection.

The Day of the Inspection

  1. Have documentation ready. Print or prepare digital access to your operations log, maintenance log, test records, fuel records, and permits. Do not make the inspector wait while you search for records.

  2. Assign an escort. Designate a knowledgeable staff member to accompany the inspector. This person should be able to explain your maintenance program, answer questions about operating history, and demonstrate generator operation if requested.

  3. Be prepared for a witnessed start. Some inspectors will want to see the generator start and the transfer switch operate. Verify that the system is in automatic mode and ready for a live demonstration.

  4. Know your system. Be prepared to state the generator's kW rating, voltage configuration, fuel type, EPA certification, and installation date. Know the nameplate details of your transfer switch.

  5. Do not argue findings. If the inspector identifies a deficiency, acknowledge it professionally and ask for clarification on the required corrective action. Request the finding in writing with the specific code reference. Disputes are resolved through the appeals process, not during the inspection.

After the Inspection

  1. Review the inspection report carefully for accuracy and completeness.
  2. Develop a corrective action plan for any cited deficiencies, with specific timelines and responsible parties.
  3. Complete corrective actions before the deadline specified by the AHJ.
  4. Document the corrective actions taken, including photographs where applicable.
  5. Submit documentation of corrective actions to the AHJ if required.
  6. Update your maintenance program to prevent recurrence of any cited deficiencies.

Maintaining Ongoing Compliance

Compliance is not a once-a-year event that coincides with your AHJ inspection. It is the result of a disciplined, year-round program that integrates inspection, testing, maintenance, and documentation into your regular facility management operations. Our weekly, monthly, and annual maintenance schedule and printable NFPA 110 test log can help.

The checklists in this guide provide the framework. Your job as a facility manager is to assign responsibility, establish accountability, and verify execution. When your program runs consistently throughout the year, AHJ inspections become confirmations of what you already know: your emergency power system is compliant, well-maintained, and ready to protect your facility and its occupants.

Sources and References

Important Disclaimer

The information provided in this article is intended for general educational purposes only and should not be considered legal, regulatory, or professional compliance advice. Content is based primarily on national standards including NFPA (National Fire Protection Association), EPA (Environmental Protection Agency), ASHRAE, and ICC (International Code Council) publications current as of the date of publication.

Compliance requirements vary significantly by state, county, and municipality. Local Authorities Having Jurisdiction (AHJs) may adopt, amend, or supplement national codes with additional requirements. Always verify applicable requirements with your local AHJ, a licensed professional engineer, or a qualified compliance consultant before making compliance decisions for your facility.

FacilityComplianceHub.org and its sponsors assume no liability for actions taken based on the information presented on this site.

Buffalo Power Solutions

This guide is brought to you by our Platinum Sponsor

Buffalo Power Solutions

Schedule a Free Compliance Assessment

Related Articles